李鹏魁, 傅允准.两级新风除湿机与毛细管辐射供热联合运行特性实验研究[J].轻工机械,2019,37(2):75-79
两级新风除湿机与毛细管辐射供热联合运行特性实验研究
Experimental Study on Joint Operation Characteristics of Two Stage Fresh Air Dehumidifier and Capillary Radiation Heating
  
DOI:10.3969/j.issn.1005 2895.2019.02.014
中文关键词:  两级新风除湿  毛细管辐射供热  供热性能  温度场
英文关键词:two stage fresh air dehumidification  capillary radiant heat supply  heating performance  temperature field
基金项目:
作者单位
李鹏魁, 傅允准 上海工程技术大学 机械与汽车工程学院 上海201620 
摘要点击次数: 1137
全文下载次数: 1117
中文摘要:
      为研究两级新风除湿机与毛细管辐射系统联合运行特性,搭建了除湿机与毛细管辐射联合供热系统实验平台,测试了除湿 机单独运行的特性及除湿机与毛细管辐射系统联合运行时室内整体温度场响应特性。实验结果表明:两级新风除湿机连续运行720 min时,新风出风平均温度约 29.7 ℃,除湿机供热量约1 545 W;两级新风除湿机不同进水温度时,随着表面式换热器进水温度的提升,新风出风温度及换热量呈规律性增加;两级新风除湿机 与毛细管辐射系统联合运行时,除湿机供热量会减小约29.1%;垂直方向温度总体呈上升趋势,在人的活动范围内,室内垂直温差较小。该系统冬季供热时,能 减小室内垂直温差,提高人体舒适性。
英文摘要:
      In order to study the combined performance of the two stage air dehumidifier and capillary radiation system, a dehumidifier and capillary radiant combined heating system experimental platform was built. The performance characteristics of separate operation of dehumidifier and the overall temperature field response in the combined operation of the dehumidifier and capillary radiation system were tested. The experimental results show that when the two stage fresh air dehumidifier continuously operates for 720 min, the average temperature of the fresh air outlet is about 29.7 ℃, the heat supply of dehumidifier is about 1 545 W; when the two stage air dehumidifier has different inlet temperatures, with the increase of the inlet water temperature of surface heat exchanger, the fresh air outlet temperature and heat exchange rate increase regularly; When the two stage fresh air dehumidifier and the capillary radiation system operated together, the heat supply of the dehumidifier will decrease by about 29.1%; the temperature in the vertical direction will generally rise, and within the range of human activities, the indoor vertical temperature difference is small. When the system is heating in winter, it can reduce the indoor vertical temperature difference and improve human comfort.